Where Passive Fire Protection Lives in Your Building
A floor-by-floor guide to fire doors, fire stopping and compartmentation in a commercial building, and what goes wrong with each.
4 min read
BM TRADA Q-Mark certified
OneTrace digital records
Written by our fire protection team
Passive fire protection is the part of a building that holds a fire where it starts. It does this without alarms, sprinklers or anyone pressing a button. Walls, floors and doors divide the building into compartments, and each compartment is built to contain fire and smoke for a set time, usually 30 or 60 minutes. That time lets people get out and lets the fire service get in.
The difficulty is that most of it is hidden. It sits in door frames, above ceilings and inside riser cupboards. This guide walks through a typical commercial building and shows where each element is, what goes wrong with it and what to do about it.
Corridors: fire doors
A fire door is a complete tested assembly: the leaf, frame, intumescent seals, hinges, closer, latch and any glazing. Change one part for something that was not in the test and the door may no longer perform.
New or replacement doors should be certified FD30 or FD60 doorsets, fitted in line with the manufacturer’s test evidence. After fitting, each door should be labelled and recorded so that anyone can check later what it is and who installed it. See our fire door installation service.
Every door, checked one by one
Fire doors are in use all day. Closers get adjusted, seals get painted over, gaps open up and doors get wedged. An inspection looks at each door in turn: the gaps around the leaf, seals, hinges, closer action, latching, glazing, signage and damage.
A good report gives you a photo of every door and a clear pass, fail or advisory rating, so you know exactly which doors need work and how urgent each one is. See our fire door inspections service.
In England, regulation 10 of the Fire Safety (England) Regulations 2022 sets minimum checks for buildings above 11 metres that contain two or more homes: fire doors in communal areas at least every three months, and best endeavours to check flat entrance doors at least every 12 months. Commercial buildings do not have the same fixed intervals, but article 17 of the Regulatory Reform (Fire Safety) Order 2005 requires fire safety measures to be maintained in an efficient state, in efficient working order and in good repair, so regular inspection is the practical way to show that. Our guide to how often fire doors should be inspected covers each building type.
Stair cores: repairs that keep the escape route protected
Stair cores are the way out, so the doors that protect them matter most. Most failed doors do not need replacing. Worn seals, a failed closer, missing hinge screws or oversized gaps can usually be put right, as long as the repair follows the door’s test evidence and uses compatible parts.
Many repairs can be done in a single visit, and each one should be recorded against the door it belongs to. See our fire door repairs service.
Risers, walls and floors: fire stopping
Every pipe, cable tray and duct that passes through a compartment wall or floor leaves a hole. If that hole is not sealed with a tested system, fire and smoke can pass straight through it, and the wall or floor will not do its job.
Fire stopping seals those penetrations with products tested for that specific service and that specific wall or floor type. Risers are the most common problem area, because new cables and pipes are added over the years and the seals are rarely made good afterwards. Each seal should be labelled, photographed and recorded. See our fire stopping service.
The whole building: compartmentation surveys
A compartmentation survey checks whether the compartment lines shown on the fire strategy drawings exist in the building as built. Surveyors look above ceilings, in risers, in plant rooms and in service voids for missing, damaged or unsuitable fire stopping, and for walls that stop short of the slab.
The result is a list of defects with locations and photos, ranked by priority, and a plan to fix them. It is the right first step if you have taken on a building and do not know its condition. See our compartmentation surveys service.
Keeping it that way: planned maintenance
A building changes every time a contractor runs a new cable or a door closer is adjusted. Planned maintenance puts fire door inspections, repairs and fire stopping checks on a schedule, floor by floor, with a record of what was found and what was done.
That record is what you show an insurer, a fire risk assessor or an enforcing authority when they ask how the building is being looked after. See our planned maintenance service.
How TECS-UK can help
TECS-UK is BM TRADA Q-Mark certified for fire door installation, fire door maintenance and fire stopping. Third-party certification means the company’s work and records are independently audited.
We carry out all six services described here for commercial clients, and every door and every seal is photographed and recorded. If you would like a survey or a second opinion on an existing report, get in touch.